Why Aren't Powergrids Underground?
jonging asks: "It is common knowledge that an underground power grid is less susceptible to the effect of a large thunderstorm. The American Transmission Company cites numerous reasons why it (and other power companies I assume) do not bury their transmission lines underground (e.g. environmental concerns, cost of installation and repair, etc.). Exactly how detrimental are underground transmission lines to the environment? Wouldn't the time spent without a power outage generate more than enough revenue to offset initial costs? Aren't the need for repairs in cities with successful underground power grids rare?" The linked article goes into extensive detail about the disadvantages in initial costs of putting in underground lines, but doesn't go into any detail about the maintenance costs of either option. With storms getting worse and worse (Maryland, DC and Northern Virginia have weathered torrential downfalls this week), might underground lines prove more resistant to storm-related power outages?
I've been building power plants and other industrial projects for 15 years now. We encase all cabling in ductbanks (conduit & rebar in concrete, usually dyed red) and only a determined idiot will knock these lines out of service.
To address the issue with power loss through induction, yet it happens and it's dangerous. We had a run of pipe being welded up directly under a 100+ kV line leaving a substation. After getting several hundred feet welded up, they started having spot fires in the area. After several calls to the local FD, the FD Chief was getting pissed so they were walking the area down, heard a zzzzzssshhhtt (best I can describe) and sure enough the lines were inducing a current into the pipe (creating a large cap) and once the charge was large enough it arced to the ground, sometimes in a area with dry leaves & pine needles.
Also on another project we had a 12kV line in a ductbank piggybacking a 100pr data cable which fed our T1/T3 lines and we kept blowing the phone companies coils on their end and causing havoc with our digital phone system. Finally one day I was re-wiring the phone system and got zapped. Voltmeter showed 60V, not sure of amerage but it smarted. Idiots who installed the 12kV line didn't bond the shield so we had a current inducted into the 100pr.
So, yes power can be run underground but you better encase it and know what you're doing or hire someone who does.