Using a House's Concrete Foundation To Cool a PC

Agg writes "Well the slab gets poured on Wednesday so I thought I would sink 6 meters of copper pipe in the slab so that I can run my water loop through it when the house is finished. I hope to have water year round at about 16deg [about 61F]. No need for radiators or fans with chilled water coming straight out of the slab!"

7 of 465 comments (clear)

  1. Don't Use Copper by Anonymous Coward · · Score: 5, Informative

    Use PEX instead. Copper will eventually fail. Look at the material that is used for radiant flooring.

  2. Re:Ice cooler! by Moryath · · Score: 5, Informative

    6 ft down doesn't actually provide much cooling. If you want a "neutral" temp, you need to go well underneath the slab.

    Plus, you're "sinking" to a temp of 40-50F, and you have to consider that the concrete itself is a fair insulator, so you won't actually lose as much heat as you hope.

  3. free cooling is, well, cool by cowscows · · Score: 5, Informative

    Ground Source heating/cooling is a pretty nifty technology, and can be applied to a whole house HVAC system, rather than just a computer. It obviously requires more tubing than a single computer would, and in most climate will still require some supplemental heating/cooling for more extreme temperature days, but it's still awesome. It does have some upfront costs though.

    This idea to do it for a particular computer is a clever idea. I personally wouldn't want the pipe to actually be moving horizontally through my slab, I'd rather dig as small a diameter hole as is possible, but deeper under the slab, and just have the line penetrate the slab vertically. The deeper you go, the more stable the temperature becomes, and the less hollow copper pipe you've got running through the slab, the less you weaken it.

    --

    One time I threw a brick at a duck.

  4. This is not a concern by name_already_taken · · Score: 5, Informative

    Houses have been built with copper pipes and steel rebar and rewire in the slab for decades now without any electrolytic effects showing up.

    Once the concrete is cured, it is no longer an electrolyte. Concrete is not a great electrical insulator, but it's not a great conductor either.

    --
    Putting moderation advice in your .sig lowers your karma!
  5. Underfloor heating, anyone? by name_already_taken · · Score: 5, Informative

    Getting rid of heat by dumping it into the ground is a great idea.

    The problem is, you're dumping heat into your house's slab, not the ground. You need to put the pipes several feet underground.

    All this is is a mild underfloor heating system. If that's what you're trying to achieve, ok, but if you're also paying for air conditioning to remove heat from the house, this is probably not worth it.

    --
    Putting moderation advice in your .sig lowers your karma!
  6. Re:Don't Use Copper - wrong by R2.0 · · Score: 5, Informative

    "Use PEX instead. Copper will eventually fail. Look at the material that is used for radiant flooring."

    Negative.

    http://www.copper.org/applications/plumbing/techcorner/problem_embedding_copper_concrete.html

    They use PEX because it is cheaper and easier to install, NOT because of its longevity.

    --
    "As God is my witness, I thought turkeys could fly." A. Carlson
  7. Re:Sell it? Get it past inspectors by Anachragnome · · Score: 5, Informative

    "Also, like a previous comment suggesting, maybe you should look into radiant heat tubing over copper."

    This. I used to live in Alaska and radiant heat slabs were very common. The problem was making sure they never went without heat in the winter. If they did, you ended up with burst pipes and a cracked slab. Big headache.

    The fix is burst-resistant flexible tubing. There is a product called Aqua-pex that fits the bill perfectly. Does not burst when frozen, has a 100-year warranty and is easy to install as it is flexible.

    The other problem with copper in concrete is that the concrete itself is corrosive. It WILL eventually eat through the pipes leading to all sorts of headaches. Usually, when this happens the only fix is drain them and cap the pipes. Most people in Alaska with radiant flooring, even when using Aqua-pex, lay down a second circuit in case there is a problem. They simply hook up the back-up.

    Another suggestion. If you DO use copper tubing, use alcohol, or some other coolant such as glycol, rather then water. You will have better heat transfer as well as less corrosion. This is, of course, assuming you have a closed loop circuit (would be foolish to have anything but).