Server Room Smells Can Be an Early Warning

Barence writes "As embarrassing as it may seem, an eggy smell in a server room needn't mean broaching the delicate subject of hygiene with a colleague. It can actually be a signal that something is about to go wrong with your server setup, as this consultant discovered after days of assuming questionable personal habits were to blame. The culprit? An expiring UPS device, sending out its own unique warning signal."

16 of 154 comments (clear)

  1. Riiiiiiiiight by Anonymous Coward · · Score: 4, Funny

    Amazing how many dying UPS devices must be hidden in my boss's office.

  2. Ooooga Booooga oh S#!t by voodoo+cheesecake · · Score: 5, Interesting

    Sulfur Dioxide. Ventilate, replace or recondition battery. If the egg smell is strong and you quit smelling it, that's olifactory fatigue and lethal levels of the gas exist.

    1. Re:Ooooga Booooga oh S#!t by MartinSchou · · Score: 4, Insightful

      If the egg smell is strong and you quit smelling it

      And how exactly do you tell if the smell is gone or your nose just gave out?

    2. Re:Ooooga Booooga oh S#!t by colonelquesadilla · · Score: 4, Informative

      You go get fresh air for a half hour or so, go back in, and see if you smell it again, if this isn't possible, you grab a coworker from a different room. I've never heard of hydrogen sulfide harming server maintenance employees, but it can and does happen in chemistry labs, even at undergrad level. I don't know about sulfur dioxide, but HS is about as poisonous as hydrogen cyanide (zyklon), the difference is only that it stinks so much people tend to flee before it kills them.

      --
      It's either false dichotomies, or the terrorists win, you decide.
    3. Re:Ooooga Booooga oh S#!t by voodoo+cheesecake · · Score: 4, Informative

      It effects your mucous membranes. Burning in your nose and throat is a good indicator. Levels of 100 parts per million are immediately dangerous to life and health. Ventilate or have someone hazwoper certified go in with a scba and retrieve the UPS. Short term exposure to "stinky" levels might not have long term effects.

  3. Can be? by bertok · · Score: 5, Funny

    "Can be an early warning?"

    "CAN be?"

    Like all IT administrators who've actually worked with server hardware, I have a heightened sense of smell, but only specifically for the smell of burning plastic. It's not a mere warning, it's an instant alarm that'll have every IT person in the room sniffing the power supplies.

    We IT people, we're like bloodhounds or something. I can smell burned plastic from across the street. I've been set off by welders at a car mechanic a block away. I've been set off by an invisibly tiny bit of cheese someone dropped into a toaster oven once... three floors down from the server room. Had me in a right panic.

    IT is all fun and games until the servers literally melt into slag. There's no repair CD for that -- and we all know that the backup tapes, while wonderful for backing up, aren't so good at the actual restoring bit. That's why they're called backup tapes, not restore tapes, see?

  4. Re:Who's minding the servers? by Anonymous Coward · · Score: 4, Funny

    "Windows in the server room?"

    You'd be surprised how many servers still run XP professional, or 2003

  5. Re:Funny, I routinely smell my servers... by Runaway1956 · · Score: 4, Interesting

    Uhhhmmm - it isn't just computers. If I notice an odd smell when I walk through the plant, I investigate. Our plant makes plastic products, and 2/3 of the time, the odd smell is just overheated plastic. But, the other 1/3 finds a problem of one sort, or another. Overheating oils are bad news, overheating capacitors are more bad news - actually, ANYTHING hot enough to give off an odor is bad news. Three weeks ago, we had a machine that was kicking our asses - the mold wouldn't open either manually, or in automatic. 4 of us went over that machine from one end to the other, multiple times. Ohmeters and voltmeters said that everything was just fine, believe it or not. Finally, I caught a whiff of something funky, opened up a solenoid from which the odor seemed to be coming, and found that half of the windings were burnt and shorting.

    The sense of smell is a valuable tool in troubleshooting and maintenance, unless you ignore it.

    --
    "Windows is like the faint smell of piss in a subway: it's there, and there's nothing you can do about it." - Charlie Br
  6. The admin gene [BOFH] by Anonymous Coward · · Score: 5, Interesting

    From the clasic BOFH :)

    "The admin gene," the PFY explains. "The ability to recognise things that users don't. A slight flicker of lighting, a whiff of hot component in the air, a fractional change in the pitch of a cooling fan - all of which the garden variety user misses in the headlong rush to read their email."

    http://www.theregister.co.uk/2008/07/04/bofh_2008_episode_24/

  7. APC UPS's by jgreco · · Score: 4, Informative

    APC UPS's have a tendency to cook their batteries as they get near the end of their lifetime. The results can be horrifying... bulging batteries, and if allowed to go on long enough, yes, even "sealed" lead acid batteries will rupture and you'll get the lovely sulfur smell.
    I recently pulled these APC batteries out of an APC Smart-UPS 1400, which had to be disassembled (including the removal/replacement of rivets) in order to get the batteries out.
    http://img221.imageshack.us/img221/171/imageyv.jpg

    1. Re:APC UPS's by jgreco · · Score: 4, Interesting

      Having worked with various standalone and both older and newer rackmount models, I would have to say that one of the most frustrating bits about APC's designs are that their battery compartments seem to be engineered to assume that batteries never bulge.

      On something like a standalone 1400, any bulging of the batteries tends to increase their width, jamming the batteries against the sides like Comic Book Guy trying to get through a turnstile.

      On the older 3U 1400's, the front of the chassis is cut-to-battery-size, and being constrained spacewise front-to-back, bulging usually happens widthwise across the batteries, forcing them bigger than the opening. This means that even if you remove the chassis top, you can't just get in there with a crowbar and forcibly eject them out the front chassis opening, you still need to unscrew the inner battery compartment partition (and maybe even remove it).

      This newer 2U 1400, though, wow, what a pain... the chassis is an artfully bent sheet of steel. If you cannot get the drawer to slide out of the battery compartment, the inner battery compartment partition is actually riveted to the chassis, so you have to drill out the rivets, and even after you get the partition removed, you only have one option for which battery to remove first, and they're taped down, so you have to use something like a crowbar to get them out, which is just vaguely scary because all the wiring for the battery tray surrounds the batteries in all the points where you need to exert force to break the tape adhesive.

      It's almost like they want it to be frustrating as all hell (maybe so you just replace the whole UPS?) while looking like they've tried to make it new and easy with their wonderful battery tray.

  8. Computers run on smoke by jgreco · · Score: 4, Funny

    Computers run on smoke... when the smoke comes out, they stop running.

  9. If they're like some IT departments I've seen... by Moraelin · · Score: 4, Insightful

    If they're like some of the IT departments I've seen, they might be working by some rule from upper management that they need to justify their existence by writing internal invoices for everything they do. It tends to result in them doing nothing until you tell them to, so they can bill you for it. The UPS could have not only the error lights on, but a binking "RED ALLERT" sign and the accompanying acoustic blare, and verily be on fire and billowing smoke, and nobody would touch it until you fill the proper form requesting them to put it out.

    Because, yes, that's another thing I've noticed that a lot of departments love, IT including: inventing bureaucracy and paperwork to discourage and delay actually having anything to do. You may need to fill in a 5 page form and draw powerpoint diagrams as to why you want the UPS doused and what are the architecture implications of that. And if you're unlucky a few meetings too, to convince some Mordac The Information Services Preventer why he should move his ass and turn that UPS off, and why his suggested workarounds (in which he'd not have to do anything) aren't quite solving the problem.

    --
    A polar bear is a cartesian bear after a coordinate transform.
  10. Re:This is interesting, can this happen? by jgreco · · Score: 4, Insightful

    A triggered fire suppression system should trip the A/C interlock, shutting down ventilation and outside air (blowing air is stupid when FM-100 or whatever is used).

    Normally, however, air may well be circulated in a fairly tight closed loop. You do not want to inject outside air without a lot of treatment; filtering and humidity are very large concerns. Drawing in extremely moist, hot air from outside and bringing it into your air supply may well be a lot more challenging than simply recycling the existing clean warm air that already has a roughly correct humidity, for example, and then what happens when it's winter and suddenly the outside air is cold and super-dry? You suddenly have a different HVAC challenge.

  11. water cooling by bananaendian · · Score: 4, Insightful

    This is why I prefer to build my new server rooms with individually cooled racks - each rack having its own AC-circulation - as well as using centralized water cooling for its efficiency and reliability. Circulating all your cooling air around the server room is simply a bad idea. When you have 1 kilometer of rack space on a single building floor, one source of contaminant, be it chemical or metal particles, will get into all the enclosures in the hall and cost you everything. And BTW UPS maintenance is something that modern IT management, especially outsourced services, have forgotten. Any veteran admin knows you need to estimate the end-of-life for their electronics AND replace them BEFORE they fail - just like AC-filters - If allow those to fail, they will have already done some damage! There's no "RAID" for burning electronics or blocked cooling air!

    --
    www.tribalnetworks.org - helping tribal people around the world to own their own means of high-tech communications
  12. Re:Funny, I routinely smell my servers... by X0563511 · · Score: 4, Interesting

    Far too many people rely on performance metrics and alarms. You're one of the ones who actually pays some attention :P

    Any time you enter the DC you should take stock:

    1. What do you hear? Perhaps an alarm through all the server noise? Unusually loud fans/ACUs? Anything unusually quiet? Other noises? (I 'predicted' an ACU failure because I heard the fan belt rubbing on something lightly shizz-shizz-shizz-shizz-shizz...)
    2. What do you smell? This article basically points this out. Could be leaking ACU coolant. Batteries dying. Burning server. Overloaded circuit, etc.
    3. What do you see? Yea, stupid I know but - does that corner of the room appear slightly dimmer? Better go check it out, a rack might be down and you haven't noticed yet.
    4. What do you feel? Vibrations through the floor? Could be an ACU about to pop a fan belt or blow a compressor.
    5. What do you feel further? Unusually dry or humid air? Temperatures etc.

    In short, you should be using every sense except taste and direct tactile feel. Anything shorter and you just aren't paying full attention.

    --