CE Risks from Argentina's Drop to 209V?
stm2 asks: "Effective yesterday at 6 PM GMT, the voltage in Argentina was dropped from 220V to 209V (without any warning). The aim of this change is to save power. According to gov' officials, it won't affect domestic appliances. As a concerned IT worker I think some high precision electric devices could be at stake. There is an ongoing national debate about it. Could the technical community at Slashdot give some insights about possible unintended effects?"
Just flip your power supply switches over to the 115V setting and you'll have more than enough power.
because they are in Argentina!
If you have any "precision electric devices" that relies on clean power from the electric company, you have been deceived. Quality precision electronics will always provide plenty of filtering and regulation of their own.
I thought that the main risk during power brown-outs was damage to AC motors from overheating. At least that's what they have mentioned on local radio stations when we've had power shortages.
Mea navis aericumbens anguillis abundat
http://quote.bloomberg.com/apps/news?pid=10000086& sid=a54gb5_g9EIQ&refer=latin_america
Apparently they've put the voltage back to 220 after reaching an agreement to buy power from Brazil.
I guess in a micro scale it doesn't save electricity - but in a macro scale several devices don't let more than X Amps go through before popping a circuit breaker, therefor the devices are pulling a constant amperage and saves power.
On a side note - I thought I remembered that the higher the voltage, the more efficient the transmission line, however I know that works for DC (If I recall TVA uses something like 50K Volt DC lines to ship power around) don't know about AC power.
I have mod points and I am not afraid to use them
As almost anything you have seen on the news from Argentina, reality is quite different.
Electricty companies have been demanding an price increment since 2 years ago, but it would be a very unpopular and "politicaly incorrect" for the government to allow it; so they need to present this as some kind of "emergency".
In the end, companies will:
a) be permited to rise prices about 25%
b) receive a direct subside from government
c) receive an indirect subside form government in form of tax excemptions, "special" fuell prices for generation, "loans" for equipment renewal, etc.
d) all of the above
Already solved with help from Brazil, Bolivia and Venezuela.
Good engineering design requires at least 5% tolerance for voltage differences. That's 11 volts at 220, and 209 should be well within the range of all line powered equipment. You simply can't design a product and expect the voltage to be within 5% regulated value.
Most equipment will run just fine with only 10-20% regulation. The problem with dropping the voltage is that the lower limit is much closer. A 10% device can handle voltages between 198 and 242, but if the utility lowers the voltage to 209, then when it's low by 10% it's at 188v, outside the range of a device capable of operating within 10% of its spec.
The reality is that most electronic devices use transformers and switching regulators to convert line voltage to a much lower voltage. As long as the device isn't consuming its maximum rated current (which will usually be 95% of the time) then it should be fine. The 5% of the time the device is actually using the regulator to its maximum capacity the regulator may fail to provide the voltage level. This erratic behavior will be about the worst you can expect. In most cases you won't even notice this.
The last major effect such a decrease may cause would be to large industrial motors. They are also often specified with a voltage range at which they can provide their rated HP. Lower voltage means a lower output. Those that are specified tightly, or have dodgy starting controls/capacitors may fail to start, but that's an indication of improper sizing/usage and not something that should be blamed on the power company. Of course, at a lower voltage they simply will not perform at the level they do with full voltage, but that is the stated goal for the gov't - to reduce power.
The negative effect for the gov't, though, is the result that people who want or need the same amount of power will simply be pulling more current (amps), stressing out the grid and transformers even more. This will affect transformers and lines that are already operating at their limit, or are about to fail anyway. It's unlikely, though entirely possible, for this action to cost them more than they are saving in the long run.
-Adam
In a simple device, the resistance is roughly constant (up to a certain point). When you decrease voltage, then the current draw actually decrease as well, thereby reducing the power consumption to the 2nd degree.
In your example, a device that draws 440W at 220V (i.e. 2.0A) has a resistance of 0.5 ohms. When you lower the voltage to 109V, that yields
and(Ignoring the fact that 1VA is not quite the same as 1W, due to inductance/capacitance).
My tester shows 213 V right now, at my house in downtown Buenos Aires. As I said in a previous post, this is just PR bs.
Switching mode power supplies take the very large raw input voltage, and draw directly from that input for only a very short time (micro seconds), but several thousand times a second (80Khz). The switch adjusts it draw time to collect the amount of power needed to support the output. If the input voltage drops, the switch adjusts to accept power for a slightly longer time. Really good switching power supplies (not like your PC) will operate on input ranging from DC to several hundred hertz.
- High Tech workers, please say NO to Union Carpenters, their Union sees fit to control our compensation.
True, but other devices act more like simple resistors, and if less voltage is applied they will consume less power. You PC will self-regulate, but your lightbulbs will get dimmer.
I'll bet that light bulbs and other "simple resistor" devices outweigh PCs and self-regulators several times over.
Tom Swiss | the infamous tms | my blog
You cannot wash away blood with blood
Some time ago, voltage was switched from 220V to 230V in Germany (and thus 380V to 400V for three phase current). There was a lot of arguing and lamenting, but nothing interesting happened. Most consumer electr(on)ic devices were rated 220V +/- 10%, while the power authorities guaranteed 220V +/- 5%. Now, devices are rated 230V +/- 10% and power is 230V +/- 5%. So most devices work within their specification, no matter if it is based on 220V or 230V. Some light bulbs rated 220V will light a tiny bit brighter while reducing ther lifetime by a few days.
I don't know how precise Argentina's power authorities can deliver electric power, but I guess they specify it with +/- 5%. They reduced power by exactly 5%, it should not harm most consumer electr(on)ic devices. All heating devices should have no problems, they work with slightly reduced power. Most electronic devices use voltage regulators, so they can accept a wide range of input voltage. Some few devices may need a very precise AC input voltage, but they should already work with some regulation device. The remainder could use an active UPS that generates a very precise output voltage no matter how "ugly" the input voltage is. Wide range power supplies, as used with many modern laptops, accept any input voltage between 90V and 260V, as long as it is AC. They won't have any problems with 230V, 209 V, 135V, 188V, or whatever you find at the next power outlet.
And the best of all: Light bulbs will life longer in Argentina. ;-)
Tux2000
Denken hilft.
208 vac is a manifestation of a 3 phase system, 120V to the ground, 208 volts between legs.
I've had enough abrasive sigs. Kittens are cute and fuzzy.
To really reduce power demand you'd have to cut both the voltage and the frequency, but that would have all kinds of nasty effects on things which depend on a consistent frequency - like standard electric clocks. You also lose the ability to connect to other grids. Needless to say, this is not a popular method of dealing with the issue.
Scientists restrict study to entire physical universe; creationist
Damm I knew I should have left work like 4 hours ao...damm clocks slowing down....